2: P
RODUCT
S
PECIFICATIONS
2-30 FC6A S
ERIES
MICROS
MART
U
SER
’
S
M
ANUAL
FC9Y-B1722
Ambient Temperature, Input Voltage, Output Voltage, I/O Simultaneous ON Ratio
When the FC6A Series MICROSmart is used in an ambient temperature of 45°C or higher, reduce the input voltage and I/O
utilization (simultaneous ON ratio: a%) according to the following diagrams. However, the following diagrams show the
temperature conditions when the FC6A Series MICROSmart is normally installed.
Note: Normally installed means the state in the diagram in "Normal Installation State" on page 3-1.
The usage conditions will also change according to the installation state. For details, see "Installation Location" on page 3-1.
■ Relay output type
24V DC Power Type
12V DC Power Type
I/O Simultaneous
ON Ratio (%)
100%50%25%0%
24.0 V
0 V
Input Voltage
28.8 V
Ambient
Temperature 55°C
Ambient
Temperature
65°C
Input I/O
26.4 V
I/O Simultaneous
ON Ratio (%)
100%0%
100V AC
0 V
Output Voltage
240V AC
Ambient
Temperature 55°C
50%
Ambient
Temperature
65°C
Output I/O
I/O Simultaneous
ON Ratio (%)
100%0%
0 V
Output Voltage
30V DC
24V DC
5V DC
Ambient
Temperature 55°C
50%
Ambient
Temperature
65°C
Output I/O
I/O Simultaneous
ON Ratio (%)
100%50%25%0%
12 V
0 V
Input Voltage
18 V
Ambient
Temperature 55°C
Ambient
Temperature
65°C
Input I/O
I/O Simultaneous
ON Ratio (%)
100%0%
100V AC
0 V
Output Voltage
264V AC
Ambient
Temperature 55°C
50%
Ambient
Temperature
65°C
Output I/O
I/O Simultaneous
ON Ratio (%)
100%0%
0 V
Output Voltage
30V DC
24V DC
5V DC
Ambient
Temperature 55°C
50%
Ambient
Temperature
65°C
Output I/O