EasyManua.ls Logo

IFM Electronic Efector 300 - Setting Analogue Value for Volumetric Flow; Setting Analogue Value for Temperature

IFM Electronic Efector 300
31 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
10.2.1 Switching between the menu levels
Change to the
submenu
Switching to the next submenu via the parameters [EF], [CFG],
[MEM], [EPD] or [SIM]�
► Selectasubmenuwith[▲]or[▼]andswitchtothesubmenu
by pressing [Enter]�
Back to the process
value display
► Wait for 30 seconds
or
► Change from the submenu to the main menu, from the main
menutotheprocessvaluedisplaywith[▲]or[▼].
10.2.2 Locking / unlocking
The unit can be locked electronically to prevent unintentional settings� On delivery:
not locked�
Locking is also possible via an IO-Link capable parameter setting tool�
Locking ► Make sure that the unit is in the normal operating mode�
► Press[▲]and[▼]simultaneouslyfor10s.
> [Loc] is displayed�
During operation: [Loc] is briefly displayed if you try to
change parameter values�
Unlocking ► Press[▲]and[▼]simultaneouslyfor10s.
> [uLoc] is displayed�
10.2.3 Timeout
If no button is pressed for 30 s during parameter setting, the unit returns to the
operating mode with unchanged parameter�
10.3 Setting the analogue value for volumetric flow
► Select [ASP1] and set the value at which the minimum value is provided�
► Select [AEP1] and set the value at which the maximum value is pro-
vided�
10.4 Setting the analogue value for temperature
► Select [ASP2] and set the value at which the minimum value is provided�
► Select [AEP2] and set the value at which the maximum value is pro-
vided�

Table of Contents