- 115 -
Function
Code
Name LED Display Setting Range Min. Unit Default Property
F4-05 to
F4-14
Reserved - 51: Slave pump enabled as
master pump
52: Switchover from
pressure mode to speed
mode
53: Slave pump address
selection terminal 1
54: Slave pump address
selection terminal 2
55: Switchover from
injection to pressure holding
56: Fault reset(not allowed
at overcurrent)
- -
★
F4-15 DI lter time 1 to 10 1 4
☆
F4-16 Terminal command
mode
Terminal command
mode
0: Two-line 1
1: Two-line 2
2: Three-line 1
3: Three-line 2
1 0
★
F4-17 Reserved - - - -
☆
F4-18 AI1 min. input AI1 min. input -11.00 to 11.00 V 0.01 V 0.02 V
☆
F4-19 Corresponding setting
of AI1 min. input
Corresponding setting
of AI1 min. input
-100.0% to 100.0% 0.1% 0.0%
☆
F4-20 AI1 max. input AI1 max. input -11.00 to 11.00 V 0.01 V 10.00 V
☆
F4-21 Corresponding setting
of AI1 max. input
Corresponding setting
of AI1 max. input
-100.0% to 100.0% 0.1% 100.0%
☆
F4-22 AI1 lter time AI1 lter time 0.000s to 10.000s 0.001s 0.010s
☆
F4-23 AI2 min. input AI2 min. input -11.00 to 11.00 V 0.01 V 0.02 V
☆
F4-24 Corresponding setting
of AI2 min. input
Corresponding setting
of AI2 min. input
-100.0% to 100.0% 0.1% 0.0%
☆
F4-25 AI2 max. input AI2 max. input -11.00 to 11.00 V 0.01 V 10.00 V
☆
F4-26 Corresponding setting
of AI2 max. input
Corresponding setting
of AI2 max. input
-100.0% to 100.0% 0.1% 100.0 V
☆
F4-27 AI2 lter time AI2 lter time 0.000s to 10.000s 0.001s 0.005s
☆
F4-28 AI3 min. input AI3 min. input -11.00 to 11.00 V 0.01 V 0.02 V
☆
F4-29 Corresponding setting
of AI3 min. input
Corresponding setting
of AI3 min. input
-100.0% to 100.0% 0.1% 0.0%
☆
F4-30 AI3 max. input AI3 max. input -11.00 to 11.00 V 0.01 V 10.00 V
☆
F4-31 Corresponding setting
of AI3 max. input
Corresponding setting
of AI3 max. input
-100.0% to 100.0% 0.1% 100.0%
☆
F4-32 AI3 lter time AI3 lter time 0.000s to 10.000s 0.001s 0.000s
☆