- 118 -
Function
Code
Name LED Display Setting Range Min. Unit Default Property
F7-06
Load speed display
coefcient
Load speed display
coefcient
0.0001 to 6.5000 0.0001 1.0000
☆
F7-07 Heatsink temperature 1 Heatsink temperature 1 0.0°C to 100°C 1°C - ●
F7-08 Reserved - - - - ●
F7-09 Accumulative running
time
Accumulative running
time
0 to 65535 h 1 - ●
F7-10 Software version 1 Software version 1 - - - ●
F7-11 Software version 2 Software version 1 - - - ●
F7-12 Software temporary
version 1
Software temporary
version 1
- - - ●
F7-13 Software temporary
version 2
Software temporary
version 2
- - - ●
Group F8: Auxiliary Functions
F8-17 Set running time Set running time 0 to 65000 h 1 h 0
☆
F8-18 Startup protection
selection
Startup protection
selection
0: Disabled
1: Enabled
1 0
☆
F8-22 Detection of short-
circuit to ground upon
power-on
Detection of short-circuit
to ground upon power-
on
0: Disabled
1: Enabled
1 1
☆
F8-23 Action selection upon
set running time
reached
Action selection upon
set running time
reached
0: Continue to run
1: Stop and report Err26
1 0
☆
F8-24 Software undervoltage
threshold
Software undervoltage
threshold
148.5 to 321.7 VAC (AC
voltage input, multiplied by
when converted to bus
voltage)
0.1 V 247.5 V
☆
F8-25 Allowed braking unit
running time
Allowed braking unit
running time
0.1s to 3600.0s 0.1s 5.0s
☆
Group F9: Fault and Protection
F9-00 Motor overload
protection selection
Motor overload
protection selection
0: Disabled
1: Enabled
1 0
☆
F9-01 Motor overload
protection gain
Motor overload
protection gain
0.20 to 10.00 0.01 2.00
☆
F9-08 Brake pipe applied
voltage
Brake pipe applied
voltage
650.0 to 800.0 V 0.1 V 780.0 V
☆
F9-12 Power input phase loss
protection selection
Power input phase loss
protection selection
0: Disabled
1: Enabled
1 1
☆
F9-13 Power output phase
loss protection selection
Power output phase
loss protection selection
0: Disabled
1: Enabled
1 1
☆