- 119 -
Function
Code
Name LED Display Setting Range Min. Unit Default Property
F9-14
Runaway speed
deviation
Runaway speed
deviation
0.50 to 50.00 Hz 0.01 Hz 10.00 Hz
☆
F9-15 Detection time of
runaway fault
Detection time of
runaway fault
0.1s to 20.0s 0.1s 10.0s
☆
F9-16 Motor temperature
protection
Motor temperature
protection
0: Disabled
1: Enabled
1 1
☆
F9-18 1st fault type 1st fault type 0: No fault
1: Reserved
2: Overcurrent during
acceleration (Err02)
3: Overcurrent during
deceleration (Err03)
4: Overcurrent at constant
speed (Err04)
5: Overvoltage during
acceleration (Err05)
6: Overvoltage during
deceleration (Err06)
7: Overvoltage at constant
speed (Err07)
8: Reserved
9: Undervoltage (Err09)
10: Servo drive overload
(Err10)
11: Reserved
12: Power input phase loss
(Err12)
13: Power output phase
loss (Err13)
14: Heatsink overheat
(Err14)
15: External device fault
(Err15)
16: Communication fault
(Err16)
17: Contactor fault (Err17)
18: Current detection fault
(Err18)
19: Motor auto-tuning fault
(Err19)
20: Reserved (Err20)
21: EEPROM read-write
fault (Err21)
1 0
☆
F9-19 2nd fault type 2nd fault type 1 0
☆