IS580 User Manual Chapter 3 Mechanical and Electrical Installation
- 39 -
User-dened Group
The user-dened menu is set to facilitate viewing and modifying of commonly used function codes. In this mode,
the display parameter uF3.02 indicates function code F3-02. You can also modify parameters in this mode as in
common editing state.
The user-dened group has already stored commonly used function codes at initialization.
It contains different function codes in the oil pressure control mode and non-oil pressure control mode (A3-00 = 0).
The following table lists the function codes in the user-dened group in non-oil pressure control mode (A3-00 = 0)
Function Code Parameter Name Function Code Parameter Name
F0-01 Control mode F0-02 Command source selection
F0-03 Main frequency source X selection F0-08 Preset frequency
F0-10 Max. frequency F0-17 Acceleration time
F0-18 Deceleration time F2-10 Torque upper limit
F8-00 Jog acceleration time F8-01 Jog deceleration time
F8-02 Jog deceleration time
Table 3-3 Function codes in the user-dened group in non-oil pressure control mode (A3-00 is set the other values)
Function Code Parameter Name Function Code Parameter Name
A3-01 Max. motor speed A3-02 System oil pressure
A3-03 Max. oil pressure A3-04 Oil pressure command slope time
A3-05 Oil pressure control Kp1 A3-06 Oil pressure control ti1
A3-07 Oil pressure control td1 A3-08 Maximum reverse motor speed
A3-09 Min. ow A3-10 Min. pressure
A3-20 AI zero drift auto correction F2-00 Speed loop proportional gain 1
F2-01 Speed loop integral time 1 F2-03 Speed loop proportional gain 2
F2-04 Speed loop integral time 2 F4-32 AI3 input lter time
The user-dened group allows adding and deleting function codes, which requires unlocking set in F7-03.
F7-03 determines whether to allow adding or deleting function codes to or from the user-dened group.
Function Code Parameter Name Setting Range Default
F7-03 Selection of unlocking
user-dened group
0: Enabled (Press PRG, ENTER to add/delete function
codes to/from the user-dened group.)
1: Disabled (You are not allowed to add/delete function
codes to/from the user-dened group.)
1