MD280 User Manual Description of Function Codes
- 147 -
Function Code Parameter Name Setting Range Default
FB-12
Judging voltage of power dip ride-
through action
60.0%–100.0% 80.0%
If the power dip ride-through function is enabled, when the bus voltage is lower than the
value of FB-12, the AC drive reduces the running frequency based on the power dip ride-
through frequency decline rate set in FB-10. When the bus voltage rises to the value of
FB-12 and remains such state for the time set in FB-11, the AC drive restores to the set
frequency.
If the bus voltage does not rise to the value of FB-12, the AC drive keeps reducing the
running frequency to 0 and then stops.
If FB-10 is set to a small value, the load feedback energy is small and the low-voltage
compensation is not effective. If FB-10 is set to a very large value, the load feedback energy
is large, which may cause overvoltage protection. Set this parameter properly based on the
inertia and load.
Figure 6-26 Power dip ride-through running
Voltage V
Bus voltage
FB-12
Output
frequency Hz
Set
frequency
FB-11
FB-10
Acceleration time 1 or 2
Time t
Time t
Function Code Parameter Name Setting Range Default
FB-13 Fault auto reset times 0–10 0
It is used to set the times of fault auto resets if this function is used. After the value is
H[FHHGHGWKH$&GULYHZLOOUHPDLQLQWKHIDXOWVWDWH
7KHIDXOWDXWRUHVHWGRHVQRWWDNHHIIHFWIRUWKHH[WHUQDOIDXOWVDQGWKHIDXOWRIUXQQLQJ
time reached.
If manual reset is performed, the fault auto reset time is cleared to 0.
The auto reset times of undervoltage faults are not counted in this parameter.
Function Code Parameter Name Setting Range Default
FB-14 DO action during fault auto reset
0: No
1: Yes
0
It is used to decide whether the DO acts during the fault auto reset if the fault auto reset
function is selected.