MD280 User Manual Function Code Table
- 91 -
Function
Code
Parameter Name Setting Range
Min.
Unit
Default
Property
F8-25
Acceleration/
Deceleration time
of simple PLC
reference 6
0–1 1 0
ƿ
F8-26
Running time
of simple PLC
reference 7
±VK VK VK
ƿ
F8-27
Acceleration/
Deceleration time
of simple PLC
reference 7
0–1 1 0
ƿ
Group F9: Reserved
F9-00 Reserved
Grouup FA: Communication Parameters
FA-00 Baud rate
1: 600 bps
2: 1200 bps
3: 2400 bps
4: 4800 bps
5: 9600 bps
6: 19200 bps
7: 38400 bps
15
ƿ
FA-01 Data format
0: No check
1: Even parity check
2: Odd Parity check
10
ƿ
FA-02 Local address
0–247
0: Broadcast address
11
ƿ
FA-03 Response delay 0–20 ms 1 ms 2 ms
ƿ
FA-04
Communication
timeout
0.0–60.0s
0.0s: invalid
0.1s 0.0s
ƿ
Group FB: Overload and Protection
FB-00
Motor overload
protection selection
0: Disabled
1: Enabled
11
ƿ
FB-01
Motor overload
protection gain
0.20–10.00 0.01 1.00
ƿ
FB-02
Motor overload pre-
ZDUQLQJFRHI¿FLHQW
50%–100% 1% 80%
ƿ
FB-03
Overvoltage stall
gain
0–100 1 0
ƿ
FB-04
Overvoltage stall
protective threshold
120%–150% 1% 130%
ƿ