Chapter 6 Parameter Description
-57-
Set up
value
Function Description
the inverter control. It
is the general method
adopted when there is
huge load and no
requirement for the stop
time. This mode is the
same as the meaning of
coast to stop as
described in F6.10.
9
Fault
reset
(RESET)
External fault reset
function. It is the same
as the function of
RESET key on the
keyboard. Using this
function can realize
long-distance fault
reset.
11
External
fault
normally
open input
After the external fault
signal is sent to the
inverter, the inverter
reports fault and stops.
12
MS
terminal 1
13
MS
terminal 2
It can realize 16S speed
through the
combination of digital
status of these two
terminals.
Refer attached table 1
for the MS speed
function description.
14
External
fault
normally
closed
After the external fault
signal is sent to the
inverter, the inverter
reports fault and stops.
Set up
value
Function Description
input
16
Reference
switch
between
AI1 and
AI2
It is enabled only when
F0-02 frequency source
selects AI1 or AI2
19
UP and
DOWN
setup
clear
(terminal
and
keyboard)
When the frequency
reference is digital
frequency reference,
this terminal can be
used to clear the
frequency value
modified by UP/DOWN
and thus restore the
reference frequency to
the setup value of
F0.04.
20
Running
command
switching
terminal
When the command
source (F0-01) is set to
1, it performs switching
between terminal
control and keyboard
control via this terminal.