Function
code
Name LED display Set range
Minim-
um unit
Factory
default
value
Modication
description
F5-11 AO1 gain AO1 gain -10.00
~
10.00 0.01 1.00
☆
F5-12
AO2 offset
coefcient
(on IO
expansion
card)
AO offset -100.0%
~
100.0% 0.1% 0.0%
☆
F5-13
AO2 gain (on
IO expansion
card)
AO2 gain -10.00
~
10.00 0.01 1.00
☆
Group F6 Start/Stop Control
F6-00 Start mode Start mode
0: Direct start
1: Speed tracking restart
1 0
☆
F6-01
Rotation
speed
tracking mode
Rotation
speed tracking
mode
0: Beginning from stop frequency
1: Beginning from zero speed
2: B egin n ing fro m maximu m
frequency
1 0
★
F6-02
Rotation
speed
tracking
speed
Rotation
speed tracking
speed
1
~
100 1 20
☆
F6-03
Start
frequency
Start
frequency
0.00 Hz
~
10.00Hz 0.01Hz 0.00Hz
☆
F6-04
Start
frequency
holding time
Start holding
time
0.0s
~
36.0s 0.1s 0.0s
★
F6-05
DC brake
current at start
Brake current
at start
0%
~
100% 1% 0%
★
F6-06
DC brake time
at start
Brake time at
start
0.0s
~
36.0s 0.1s 0.0s
★
F6-07
speed-up/
speed-down
mode
speed-up/
speed-down
mode
0: Straight speed-up/speed-down
1: S-cruve speed-up/speed-down
1 0
★
F6-08
Start segment
time of S
curve
Start segment
of S curve
0.0%
~
40.0% 0.1% 30.0%
★
F6-09
End segment
time of S
curve
Start segment
of S curve
0.0%
~
40.0% 0.1% 30.0%
★
F6-10 Stop mode Stop mode
0: Speed-down to stop
1: Free stop
1 0
☆
F6-11
DC brake
beginning
frequency at
stop
Brake
frequency at
stop
0.00Hz ~ maximum frequency 0.01Hz 0.00Hz
☆