Function Parameter Table MD320/MD320N User Manual
92
Function
code
Name LED display Set range
Minim-
um unit
Factory
default
value
Modication
description
FC-50
Running time
of PLC
Time unit
selection
0: s(s)
1: h(h)
1 0
☆
Group FD Communication Parameters
FD-00 Baud rate Baud rate
0
:
300BPS
1
:
600BPS
2
:
1200BPS
3
:
2400BPS
4
:
4800BPS
5
:
9600BPS
6
:
19200BPS
7
:
38400BPS
1 5
☆
FD-01 Data format Data format
0: No parity check
1: Even parity check
2: Odd parity check
1 0
☆
FD-02 Local address Local address
1 to 247, and 0 is the broadcast
address.
1 1
☆
FD-03
response
delay
response
delay
0ms
~
20ms 1 2
☆
FD-04
Communi-
cation timeout
time
Communi-
cation timeout
time
0.0(inactive),and 0.1 ~ 60.0.0s 0.1s 0.0
☆
FD-05
communi-
cation
protocol
selection
communi-
cation protocol
selection
0:Non-standard MODBUS
protocol
1: Standard MODBUS protocol
1 0
☆
Group FE Reserved Function Group
Group FF Factory Parameters
FF-00
Manufacturer
password
Manufacturer
password
Reserved
Reserv-
ed
Reserved
﹡
Group F User Password
FP-00
User
password
User
password
0
~
65535 1 0
☆
FP-01
Parameter
initialization
Parameter
initialization
0: No operation
1: Restore factory default setup
value
2: Clear the fault record
1 0
★