MD380 User Manual Function Code Table
- 101 -
)unction
Code
Parameter Name
Setting Range
Default Property
)8-47
Module temperature
threshold
0–100°C
75
°C
ƿ
)8-48 Cooling fan control
)DQZRUNLQJGXULQJUXQQLQJ
)DQZRUNLQJFRQWLQXRXVO\
0 ƿ
)8-49 Wa
keup frequency
'RUPDQWIUHTXHQF\)WR
PD[LPXPIUHTXHQF\)
0.00 Hz ƿ
)8-50 Wa
keup delay time
0.0–6500.0s
0.0s ƿ
)8-51 Dormant frequency
+]WRZDNHXSIUHTXHQF\)
49)
0.00 Hz ƿ
)8-52 Dormant delay time
0.0–6500.0s
0.0s ƿ
)8-53
Current running time
reached
0.0–6500.0 min
0.0 min ƿ
)8-54
Output power correction
coef¿cient
0.00%–200 .0%
100.0% ƿ
Group )9: )ault and Protection
)9-00
Motor overload protection
selection
0: Disabled
1: Enabled
1 ƿ
)9-01
Motor overload protection
gain
0.20–10.00
1.00 ƿ
)9-02
Motor overload warning
coef¿cient
50%–100%
80% ƿ
)9-03 Overvoltage stall gain
0 (no stall overvoltage)–100
0 ƿ
)9-04
Overvoltage stall protective
voltage
120%–150%
130% ƿ
)9-05 Overcurrent stall gain
0–100
20 ƿ
)9-06
Overcurrent stall protective
current
100%–200%
150% ƿ
)9-07
Short-circuit to ground upon
power-on
0: Disabled
1: Enabled
1 ƿ
)9-09 )ault auto reset times
0–20
0 ƿ
)9-10
DO action during fault auto
reset
0: Not act
1: Act
0 ƿ
)9-11
Ti
me interval of fault auto
reset
0.1s–100.0s
1.0s ƿ
)9-12
Input phase loss protection/
contactor energizing
protection selection
Unit's digit: Input phase loss
protection
Ten's digit: Contactor energizing
protection
0: Disabled
1: Enabled
11 ƿ