Function Code Table
MD380 User Manual
- 102 -
)unction
Code
Parameter Name
Setting Range
Default Property
)9-13
Output phase loss protection
selection
0: Disabled
1: Enabled
1 ƿ
)9-14 1st fault type
0: No fault
1: Reserved
2: Overcurrent during acceleration
3: Overcurrent during deceleration
4: Overcurrent at constant speed
5: Overvoltage during
acceleration
6: Overvoltage during
deceleration
7: Overvoltage at constant speed
%XIIHUUHVLVWDQFHRYHUORDG
9: Undervoltage
10: AC drive overload
11: Motor overload
12:Power input phase loss
13: Power output phase loss
14: Module overheat
15: External equipment fault
16: Communication fault
17: Contactor fault
18: Current detection fault
19: Motor auto-tuning fault
20: Encoder/PG card fault
21: EEPROM read-write fault
22: AC drive hardware fault
23: Short circuit to ground
24: Reserved
25: Reserved
26: Accumulative running time
reached
8VHUGH¿QHGIDXOW
8VHUGH¿QHGIDXOW
29: Accumulative power-on time
reached
30: Load becoming 0
31: PID feedback lost during
running
- ƽ
)9-15 2nd fault type - ƽ