MD380 User Manual Desc
ription of Function Codes
- 201 -
)unction Code Parameter Name Setting Range Default
)9-12
Input phase loss
protection/contactor
energizing protection
selection
Unit's digit: Input phase loss protection
Te
n's digit: Contactor energizing
protection
0: Disabled
1: Enabled
11
It is used to determine whether to perform input phase loss or contactor energizing
protection.
The MD380 models that provide this function are listed in the following table.
Table 6-8 MD380 models providing the input phase loss or contactor energizing protection
function
Voltage Class Models
Single-phase 220 V None
Three-phase 220 V 11
kW G model
Three-phase 380 V 18.5 kW G model
Three-phase 690 V 18.5 kW G model
)RUHYHU\YROWDJHFODVVWKH0'$&GULYHVRISRZHUVHTXDOWRRUJUHDWHUWKDQWKRVH
listed in the preceding table provide the function of input phase loss or contactor energizing
protection. The MD380 AC drives below the power listed in the table do not have the
IXQFWLRQQRPDWWHUZKHWKHU)LVVHWWRRU
)unction Code Parameter Name Setting Range Default
)9-13 Output phase loss protection selection
0: Disabled
1: Enabled
1
It is used to determine whether to perform output phase loss protection.
)unction Code Name Setting Range
)9-14 1st fault type
0–99)9-15 2nd fault type
)9-16 3rd (latest) fault type
It is used to record the types of the most recent three faults of the AC drive. 0 indicates no
IDXOW)RUSRVVLEOHFDXVHVDQGVROXWLRQRIHDFKIDXOWUHIHUWR&KDSWHU
)unction Code Parameter Name Description
)9-17 )requency upon 3rd fault
It displays the frequency when the latest fault
occurs.
)9-18 Current upon 3rd fault
It displays the current when the latest fault
occurs.
)9-19 %us voltage upon 3rd fault
It displays the bus voltage when the latest fault
occurs.