EasyManua.ls Logo

Inovance MD380-5T5.5GB - Page 82

Inovance MD380-5T5.5GB
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MD380 User Manual Function Code Table
- 81 -
)unction
Code
Parameter Name
Setting Range
Default Property
)0-03
Main frequency source X
selection
5: Pulse setting (DI5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication setting
0 ƾ
)0-04
Auxiliary frequency source Y
selection
7KHVDPHDV)0DLQ
frequency source X selection)
0 ƾ
)0-05
Range of auxiliary frequency
Y
for X and Y operation
0: Relative to maximum frequency
1: Relative to main frequency X
0 ƿ
)0-06
Range of auxiliary frequency
Y
for X and Y operation
0%–150%
100% ƿ
)0-07 )requency source selection
8QLWVGLJLW)UHTXHQF\VRXUFH
selection)
00 ƿ
0: Main frequency source X
1: X and Y operation
(operation relationship determined
by ten's digit)
2: Switchover between X and Y
3: Switchover between X and "X
and Y operation"
4: Switchover between Y and "X
and Y operation"
Ten's digit (X and Y operation
relationship)
0: X+Y
1: X-Y
2: Maximum
3: Minimum
)0-08 Preset frequency
0.00 to maximum frequency (valid
when frequency source is digital
setting)
50.00 Hz ƿ
)0-09 Rotation direction
0: Same direction
1: Reverse direction
0 ƿ
)0-10 Maximum frequency
50.00–320.00 Hz
50.00 Hz ƾ
)0-11
Source of frequency upper
limit
6HWE\)
1: AI1
2: AI2
3: AI3
4: Pulse setting (DI5)
5: Communication setting
0 ƾ