Technical Data
‑154‑
Table 6–10 Electrical parameters of T7 to T8 models (three‑phase 200 V to 240 V)
Item
Specification
Module: MD520‑2Txxxxx
22(B)(S) 30(B)(S) 37(B)(S) 45(S) 55(S)
Structure T7 T8
Output Power (kW) (heavy load)
22 30 37 45 55
Power (kW) (light load)
30 37 45 55 75
Rated output current (A)
(heavy load)
91 112 150 176 210
Rated output current (A) (light
load)
112 150 176 210 253
Output voltage Three‑phase 0 V to input voltage
Maximum output frequency 599 Hz (edited through parameters)
Carrier frequency
0.5 kHz to 16.0 kHz (automatically adjusted according to the load
characteristics)
Overload capacity
Heavy load: 60s at 150% of the rated current
Light load: 60s at 110% of the rated current
Input Rated input current (A) (heavy
load)
89 106 139 164 196
Rated input current (A) (light
load)
111 153 167 198 239
Rated voltage and frequency Three‑phase 200 V to 240 V, 50/60 Hz
Allowable voltage fluctuation
range
‑15% to +10%, or 170 VAC to 264 VAC
Allowable frequency
fluctuation range
±5%, or 47.5 Hz to 63 Hz
Power supply capacity (kVA)
(heavy load)
40.7 48.5 63.6 75 89.6
Power supply capacity (kVA)
(light load)
48.5 63.6 75 89.6 109
Heat
Dissipation
Design
Thermal design power (kW)
(heavy load)
1.01 1.21 1.57 1.81 2.14
Thermal design power (kW)
(light load)
1.21 1.57 1.81 2.14 3.56
Exhaust air volume (CFM)
122.2 122.2 218.6 287.2 354.2
Overvoltage
class
OVCIII
Pollution
degree
PD2
IP rating
IP20