Technical Data
‑155‑
Table 6–11 Electrical parameters of T9 to T12 models (three‑phase 200 V to 240 V)
Item
Specification
Module: MD520‑2Txxxxx
75(S) 90(S) 110(S) 132(S) 160(S) 200(S)
Structure T9 T10 T11 T12
Output Power (kW) (heavy load)
75 90 110 132 160 200
Power (kW) (light load)
90 110 132 160 200 220
Rated output current (A)
(heavy load)
304 377 426 465 585 725
Rated output current (A) (light
load)
377 426 465 585 725 880
Output voltage Three‑phase 0 V to input voltage
Maximum output frequency 599 Hz (edited through parameters)
Carrier frequency
0.5 kHz to 16.0 kHz (automatically adjusted according to the load
characteristics)
Overload capacity
Heavy load: 60s at 150% of the rated current
Light load: 60s at 110% of the rated current
Input Rated input current (A) (heavy
load)
287 365 410 441 565 687
Rated input current (A) (light
load)
359 456 507 559 708 840
Rated voltage and frequency Three‑phase 200 V to 240 V, 50/60 Hz
Allowable voltage fluctuation
range
‑15% to +10%, or 170 VAC to 264 VAC
Allowable frequency
fluctuation range
±5%, or 47.5 Hz to 63 Hz
Power supply capacity (kVA)
(heavy load)
131 167 187 202 258 314
Power supply capacity (kVA)
(light load)
164 209 232 256 324 384
Heat
dissipation
design
Thermal design power (kW)
(heavy load)
3.56 4.15 4.55 5.33 5.69 6.91
Thermal design power (kW)
(light load)
4.15 4.55 5.33 5.69 6.91 7.61
Exhaust air volume (CFM)
627 638.4 722.5 882 645 860
Overvoltage
class
OVCIII
Pollution
degree
PD2
IP rating
IP20