Quick Operation
‑32‑
Param
eter
Code
Parameter Name
Value Range
Description
A2‑24
Performance
software sub‑
version
0.00‑655.35
This parameter displays the
temporary performance software
version.
A2‑25
Function software
sub‑version
0.00‑655.35
This parameter displays the
temporary function software version.
Note
Parameters in the preceding table cannot be changed.
6.3.5 Setting Motor Parameters
Set motor parameters according to the motor nameplate, including the rated motor
power, voltage, current, frequency, and speed, motor power factor, maximum
frequency, and minimum frequency.
Param
eter
Code
Parameter
Name
Value Range
Description
C4‑01
Rated motor
power
0.1 kW to 1000.0
kW
The rated motor power indicates the axis
output power of the motor working in rated
conditions. Select a motor with a proper
power rating on the premise that the motor
can meet the requirements of mechanical
load. Take the motor heat dissipation,
allowable overload capacity, and starting
capacity into account.
C4‑03
Rated motor
voltage
1 V to 2000 V
The rated motor voltage indicates the voltage
of the motor during normal operation, which
usually refers to the line voltage.
C4‑04
Rated motor
current
0.1 A to 6553.5 A
The rated motor current indicates the current
of the motor during normal operation, which
usually refers to the line current.
C4‑06
Rated motor
frequency
0.01 Hz to 599 Hz
The rated motor frequency indicates the
frequency of the power supply connected to
the stator winding under the rated operation
conditions of the motor.
C4‑07
Rated motor
speed
1 RPM to 65535
RPM
The rated motor speed indicates the speed
(r/min) of the rotor when the motor is
running under rated conditions.