Quick Operation
‑36‑
4. When the AC drive is running, press to stop the AC drive (the RUN
indicator is off).
The following table describes parameters related to the command source.
Table 6–5 Related parameter
Param
eter
Code
Parameter Name De
fault
Value Range
Description
b0‑02 Control channel
selection
0
0: Control channel 1
1: Control channel 2
3: DI1
4: DI2
5: DI3
6: DI4
7: DI5 (MD600A)
Others: B connector
This parameter is used to
select the control channel.
When it is set to 0, control
channel 1 is selected. When
it is set to 1, control channel
2 is selected.
b1‐00 Command source of
control channel 1
0
0: Operating panel
1: Terminal
2: Communication
3: User‑defined
This parameter is used to
select the command source
of control channel 1.
0: LCD operating panel or
SOP operating panel
1: DI (select the related
function of the DI)
2: Communication control
such as the Modbus
3: User‑defined source (such
as terminal, OFF1, OFF2, or
OFF3)
b3‑00 Command source of
control channel 2
0
0: Operating panel
1: Terminal
2: Communication
3: User‑defined
This parameter is used to
select the command source
of control channel 2.
0: LCD operating panel or
SOP operating panel
1: DI (select the related
function of the DI)
2: Communication control
such as the Modbus
3: User‑defined source (such
as terminal, OFF1, OFF2, or
OFF3)
6.3.8 Setting the Frequency Source
Set b5‑00 or b6‑00 to select a frequency source. The frequency source indicates the
running frequency source or input source.