Common Parameter Settings
‑54‑
8 Common Parameter Settings
The following table describes certain common parameters in brief. The parameter
modification modes are as follows:
● Unchangeable
● At stop
● Real time
For details on the complete parameter list, see "List of Parameters" in the
MD600
Series Basic AC Drive Function Guide
.
Param
eter
Code
Commu
nication
Address
Parameter Name Value Default Unit Change
Mode
F0‑00 0xF000 Load type 0: Heavy load application
1: Light load application
0 ‑ Unchangea
ble
F0‑01 0xF001 Motor control
mode
2: V/f 2 ‑ Unchangea
ble
F0‑02 0xF002 Motor control
method
0: Speed control
1: Torque control
2: Terminal input
3: DI1
4: DI2
5: DI3
6: DI4
7: DI5 (MD600A)
Others: B connector
0 ‑ Unchangea
ble
F0‑03 0xF003 Command source
of control channel
1
0: Operating panel
1: Terminal
2: Communication
3: Customized
0 ‑ At stop
F0‑07 0xF007 Mode of terminal
start/stop module
A
0: Disable
1: IN1 is used to start the AC drive.
2: IN1 is used to start the AC drive, and IN2
is used to set the direction.
3: IN1 is used for forward start, and IN2 is
used for reverse start.
4: IN1P (rising edge) is used to start the AC
drive, and IN2 is used to stop the AC drive.
5: IN1P (rising edge) is used to start the AC
drive, IN2 is used to stop the AC drive, and
IN3 is used to set the direction.
6: IN1P (rising edge) is used for forward
start, IN2P (rising edge) is used for reverse
start, and IN3 is used to stop the AC drive.
3 ‑ At stop