Quick Operation
‑33‑
Param
eter
Code
Parameter
Name
Value Range
Description
C4‑09 Motor power
factor
0.600‑1.000
This parameter indicates the parameter
power factor on the motor nameplate.
C4‑10 Maximum
motor
frequency
C4‑06 to 599.00 Hz
This parameter indicates the allowed
maximum frequency of the motor.
C4‑11
Minimum
motor
frequency
0.00 Hz to C4‑10
This parameter indicates the allowed
minimum frequency of the motor.
6.3.6 Performing Motor Parameter Auto-tuning
The procedure for motor parameter auto‑tuning is as follows:
1. Enter motor nameplate parameters (C4‑01 to C4‑11) correctly. For details, see "
6.3.5
Setting Motor Parameters
"
on page 32
.
2. Set C2‑00 to 1 (partial static auto‑tuning of asynchronous motor).
3. Press the OK key. "TUNE" is displayed on the operating panel.
4. Press the OK key to start auto‑tuning. When "50.00" is displayed, the auto‑tuning is
completed.