Table 6–7 Related parameter
Param
eter
Code
Parameter
Name
Default Value Range
Description
b7‑01
Ramp
accelera
tion/
deceleration
time base
frequency
0 0 to 3
It is used to select acceleration/
deceleration time base frequency.
Acceleration time indicates time
required by the AC drive to accelerate
from 0 Hz to the ramp acceleration/
deceleration time base frequency.
Deceleration time indicates time
required by the AC drive to decelerate
from the ramp acceleration/
deceleration time base frequency to 0
Hz.
b7‐04
Ramp 1
acceleration
time
20.0s 0.0s to 6500.0s
It indicates the time required for the
output frequency to increase from 0 to
the ramp acceleration/deceleration
time base frequency (b7‑01). The time
is used to set the accelerated speed
during acceleration.
The AC drive provides four groups of
acceleration/deceleration time, which
can be selected by using the parameter
or DI. This parameter specifies the first
acceleration time.
b7‐05
Ramp 1
deceleration
time
20.0s 0.0s to 6500.0s
It indicates the time required for the
output frequency to decrease from the
ramp acceleration/deceleration time
base frequency (b7‑01) to 0. The time is
used to set the accelerated speed
during deceleration.
The AC drive provides four groups of
acceleration/deceleration time, which
can be selected by using the parameter
or DI. This parameter specifies the first
deceleration time.
6.3.10Setting Stop Mode Parameters
Under normal working conditions, the AC drive stops running according to the OFF1
stop mode. The procedure is as follows:
1. Set d0‑04 (OFF1 stop mode) to 0 (decelerate to stop).
2. Set F0‑30 (running frequency) to 50.00 Hz. For details, see "
6.3.9 Setting the
Acceleration/Deceleration Time
"
on page 44
.