Common Parameter Settings
‑58‑
Param
eter
Code
Commu
nication
Address
Parameter Name Value Default Unit Change
Mode
F0‑21 0xF015 DO1 function
selection (for
MD600A)
0: No output
1: AC drive running
2: Fault output
3: Frequency level detection FDT1 output
4: Frequency reach
5: Zero‑speed running (no output at stop)
6: Motor overload warning
7: AC drive overload warning
8: Set count value reach
9: Designated count value reach
10: Length reach
11: Simple PLC cycle completed
12: Cumulative running time reach
13: Wobble frequency limited
14: Torque limited
15: Ready to run
17: Frequency upper limit reach
18: Frequency lower limit reach (no output
at stop)
19: Undervoltage output
20: Communication setting
23: Zero‑speed running 2 (output at stop)
24: Cumulative power‑on time reach
25: Frequency level detection FDT2 output
26: Output upon frequency 1 reach
27: Output upon frequency 2 reach
28: Output upon current 1 reach
29: Output upon current 2 reach
30: Output upon expiration of scheduled
time
31: AI1 input limit exceeded
32: Three‑phase loss
33: Reverse running
34: Zero current state
35: Module temperature reach
36: Output current limit exceeded
37: Frequency lower limit reach (output at
stop)
38: Output upon fault, minor fault, or
warning
40: Current running time reach
41: Output upon fault (excluding
undervoltage)
43: Output upon minor fault or warning
Others: B connector
1 ‑ Real time