Common Parameter Settings
‑73‑
Param
eter
Code
Commu
nication
Address
Parameter Name Value Default Unit Change
Mode
A3‑03 0xA303 Rated AC drive
current
0.0 A to 6553.5 A 9.5 A Unchangea
ble
A3‑04 0xA304 Rated AC drive
voltage
0 V to 65535 V 380 V Unchangea
ble
A3‑05 0xA305 Maximum AC drive
current
0% to 600% 150 % Real time
A3‑06 0xA306 AC drive hardware
type
0: MD600A (CAN version)
4: MD600S (Modbus version)
0 ‑ Unchangea
ble
A3‑51 0xA333 Module
overtemperature
threshold
0°C to 65535°C 0 °C Unchangea
ble
A3‑55 0xA337 Undervoltage
threshold
150.0 V to 440.0 V 350.0 V Real time
A3‑56 0xA338 Valid undervoltage
threshold
150.0 V to 440.0 V 350.0 V Unchangea
ble
A3‑57 0xA339 Overvoltage
threshold
300.0 V to 820.0 V 820.0 V Real time
A3‑58 0xA33A Valid overvoltage
threshold
300.0 V to 820.0 V 820.0 V Unchangea
ble
A4‑00 0xA400 Braking unit action
voltage
300.0 V to 820.0 V 760.0 V At stop
A4‑01 0xA401 Active braking unit
action voltage
300.0 V to 820.0 V 760.0 V Unchangea
ble
A4‑11 0xA40B Fan control mode 0: The fan works forwardly when the AC
drive is running. In the stop state, the fan
works when the temperature is higher
than 42°C.
1: The fan works forwardly.
2: The fan works forwardly or reversely
when the AC drive is running. In the stop
state, the fan works when the temperature
is higher than 42°C.
3: The fan always works forwardly or
reversely.
4: Speed digital setting
5: Intelligent fan mode
0 ‑ Real time
A4‑12 0xA40C Digital setting of
fan speed
1500 RPM to 14000 RPM 1500 RPM Real time
A4‑13 0xA40D Valid value of
digital setting for
fan speed
1500 RPM to 14000 RPM 1500 RPM Unchangea
ble
A4‑14 0xA40E Forward running
time of fan in
forward/reverse
running mode
60s to 65535s 60 s Real time