5 System Commissioning
-
156
-
b) Asynchronous motor no-load auto-tuning
Enter the emergency electric RUN state
Set motor type:
F
1-
25 = 0
Set encoder parameters:
F
1-00 and
F1-12
Set motor parameters:
F1
-01
to F
1-
05
Check F0
-01
=
0
F1-
11 = 2
X9
indicator on the MCB is OFF, indicating that the elevator enters the emergency
electric RUN state.
Set F
1-
25
to 0
.
Obtain the rated motor power, rated motor voltage,
rated motor current, rated
motor frequency, and rated motor speed from the motor nameplate.
Be sure that motor parameters are set correctly. Otherwise, faults will occur.
Set F1-00 according to the actual encoder type.
0
: SIN
/
COS encoder; 1: UVW Encoder; 2: ABZ Encoder; 3: Endat encoder
Set F1
-12
(
Encoder pulses per revolution) according to the encoder nameplate.
F
0
-01
must be set to 0 during no
-
load auto-
tuning.
Auto-
tuning completed
During no-load auto-
tuning, the motor rotates, but the brake must be released
manually. The auto-tuning process lasts about several tens of seconds.
After auto-tuning is completed,
the controller stops output automatically.
Five parameters F1-14
to F1-
18 are obtained.
After setting F
1-11 to 2, press ENTER. If the operation panel displays "TUNE", the
system enters the motor auto-
tuning state.
If the operation panel displays "F1-12", the system fails to enter motor auto-
tuning state.
You need to check
:
Whether the elevator is in emergency electric RUN state.
Whether the MCB displays faults to be rectified.
Whether F0-01 is set to 0.
Perform auto-tuning
:
Release the brake manually.
Press the RUN key
on the operation
panel to start auto
-tuning.
Restore F0-01 to
1
After auto
-tuning is completed, F0-01 must be restored to 1. Otherwise,
the elevator
cannot run.
󶙽Asynchronous motor no-load auto-tuning
Pay attention to the following precautions during asynchronous motor auto-tuning:
The sequence of encoder phases A and B must be correct. If the sequence is
incorrect, fault Err38 is reported. To solve the problem, exchange phases A and B of
the encoder.
The system handles the output commands to the RUN contactor or brake contactor
󶍽󶍽