6 Parameter Description
-
186
-
the drive board is consistent with the UVW phase sequence of the motor. If the value
obtained by means of no-load auto-tuning is an even number, the phase sequence is
correct. If the value is an odd number, the sequence is incorrect; in this case, exchange
any two of UWW phases of the motor.
Function
Code
Name Setting Range Default Unit Property
F1-09
(synchronous motor)
0.0 to 359.9 0 -
★
Function
Code
Name Setting Range Default Unit Property
F1-10
selection
0 to 65535 0 -
★
-
turer, and you need not modify it generally.
Function
Code
Name Setting Range Default Unit Property
F1-11 Auto-tuning mode
0: No operation
1: With-load auto-
tuning
2: No-load auto-tuning
3: Shaft auto-tuning 1
4: Shaft auto-tuning 2
5: Synchronous motor
static auto-tuning
0 -
★
It is used to select the auto-tuning mode. The values are as follows:
■
0: No operation;
■
1: With-load auto-tuning: static auto-tuning for asynchronous motor and rotary
auto-tuning for synchronous motor;
■
2: No-load auto-tuning;
■
3: Shaft auto-tuning 1, cleaning no parameters in group FR;
■
4: Shaft auto-tuning 2, cleaning parameters in group FR;
■
5: Synchronous motor static auto-tuning.