6 Parameter Description
-
192
-
curve (start jerk segment). The larger the value is, the smoother the jerk is.
Figure 6-2 shows the settings of the entire running curve.
F3-02 (F3-05) is the acceleration (deceleration) rate of the speed curve in the linear
acceleration process.
F3-03 (F3-07) is the time for the rate to change from 0 to the value set in F3-02 (F3-05)
in the speed curve (start jerk segment). The larger the value is, the smoother the jerk
is.
F3-04 (F3-06) is the time for the rate to decrease from the value set in F3-02 (F3-05) to
0 in the speed curve (end
jerk segment). The larger the value is, the smoother the jerk is.
t (time)
V (speed)
F3-04
F3-02
F3-03
F3-09
F3-07
F3-05
F3-06
F3-01
F3-00
Running speed curve
t (time)
a
(acceleration rate)
F3-02
F3-05
F3-03
F3-04
F
3-07
F3
-06
Acceleration rate curve
Function
Code
Name Setting Range Default Unit Property
F3-08
Special deceleration
rate
0.200 to 1.500 0.900 m/s
2
★
F3-08 is used to set the deceleration rate in elevator level 4 fault, inspection, shaft
This parameter is not used during normal running. It is used only when the elevator
position is abnormal or the slow-down signal is abnormal, preventing over travel top
terminal or over travel bottom terminal.