6 Parameter Description
-
247
-
FC-00 Program control selection
Bit Function Description Default
Bit9
Mode without door
open/close limit
In this mode, the door open/close limit signal is not
required, and the system automatically judges door
open/close limit. The system determines that door
open limit is implemented 3s after the door open
command is output and door close limit is
implemented 3s after the door close command is
output.
0
Function
Code
Name Setting Range Default Unit Property
FC-01 Function selection 0 to 65535 65 -
★
These parameters are used to select program control functions. If a bit is set to 1, the
function indicated by this bit is enabled; if this bit is set to 0, the function is disabled.
FC-01 Function selection
Bit Function Description Default
Bit0 Overload protection
0: Motor overload detection enabled
1: Motor overload detection disabled
1
Bit1
Canceling protection
at output phase loss
It sets whether to implement protection at output
phase loss.
0
Bit4
Light curtain
judgment at door
close limit
At door close limit, the door re-opens if the light
curtain is valid.
0
Bit5
Canceling SPI
communication
judgment
It sets whether to implement wire-breaking
detection on SPI communication between the MCB
and the drive board.
0
Bit6 Reserved - 0
Bit8 Reserved - 0
Bit14
Canceling protection
at input phase loss
Canceling protection at input phase loss 0