3 Peripheral Devices and Options
-
87
-
Controller
Model
Recommended
Fuse on the
Input Side
Bussmann FWH
Series
Recommended
Circuit Breaker
(A)
Recommended
Contactor
(A)
Recommended
Main Circuit
Cable
(mm
2
)
Recommended
Control Cable
(mm
2
)
Recommended
Grounding Cable
(mm
2
)
NICE-
L-C-4015
FWH-60B 50 38 6 0.75 6
NICE-
L-C-4018
FWH-70B 63 40 10 0.75 10
NICE-L-C-
4018F
NICE-
L-C-4022
FWH-80B 80 50 10 0.75 10
NICE-L-C-
4022F
NICE-
L-C-4030
FWH-100B 100 65 16 0.75 16
NICE-L-C-
4030F
NICE-
L-C-4037
FWH-125B 100 80 25 1.0 16
NICE-L-C-
4037F
NICE-
L-C-4045
FWH-150B 160 95 35 1.0 16
NICE-L-C-
4045F
NICE-
L-C-4055
FWH-200B 160 115 50 1.0 25
NICE-L-C-
4055F
NICE-
L-C-4075
FWH-275A 225 170 70 1.0 35
NICE-L-C-
4075F
NICE-
L-C-4090
FWH-300A 250 205 95 1.0 50
NICE-
L-C-4110
FWH-350A 315 245 120 1.0 60
NICE-
L-C-4132
FWH-400A 350 300 120 1.0 60
NICE-
L-C-4160
FWH-500A 400 300 150 1.0 75