Keypad
‑66‑
After this function is enabled, all DI signal levels are controlled by the forced DI
setting (H0d.18), independent of external DI signal status.
■ Operating procedure:
Figure 5‑6 Procedure for setting forced DI function
Related parameters:
Param. No.
Name
Value Range
Function
Setting
Condition
Effective
Time
Default
Keypad
Side
Software
Tool Side
H0d.17 200d.12h
Forced DI/
DO
selection
0: No operation
1: Forced DI enabled, forced
DO disabled
2: Forced DO enabled, forced
DI disabled
3: Forced DI and DO enabled
4: Profinet forced DO
enabled
Forced DI/DO
selection
During
running
At once 0
H0d.18 is used to set the forced DI level. The keypad displays the value in
hexadecimal. After the hexadecimal value is converted to a binary value, the
value "1" indicates high level and "0" indicates low level.
The DI logic is defined by parameters in group H03. H0b.03 is used to monitor
the DI level status. The keypad displays the level, and the value of H0b.03
(Monitored DI signal) read in the software tool is hexadecimal.