STEP 2 - Load inertia ratio setting
Please, refer to the section 6.6.1 Inertia Auto-tuning
STEP 3 - Rigidity Setting
The value range of H09-01 (Stiffness level selection) is 0 to 41. The level 0 indicates the weakest stiffness and
lowest gain and level 41 indicates the strongest stiffness and highest gain.
Please, refer to the section 6.6.5 Rigidity level calculation
Vibration suppression control
Vibration: Parameter H09-11-Vibration threshold. When the torque ripple detected by the servo drive exceeds
the setpoint of H09-11 and becomes uncontrollable, the stiffness level will be reduced automatically until
reaching level 10 where ER661 is reported.
Vibration suppression switch:
Parameter H09-37 - Vibration monitoring time
• Open →H09-37 = 65536
• Close →H09-37 = 0
• Default (10 minutes) →H09-37 = 600
If H09-00 (Gain auto-tuning mode) is set to 3, 4, or 6, the servo drive suppresses vibration by performing inertia
auto-tuning automatically within 10 min (or other time interval defined by H09-37) after power-on or stiffness
level setting, and then it exits from inertia auto-tuning. The inertia auto-tuning function, once deactivated,
cannot be activated again by setting H09-09 to 3, 4, or 6.