31
6.1.5.1.1.6. Rate calculation
Function - Enables or disables the counter increment computation after
the previous readout
Data type - Selection list
Variation
range
- Yes
Each activation of the module by the Measurement
timer causes the computation of counter content
increment, compared to the previously read value. The
possible crossings of Hi alarm and Lo alarm levels are
tested as well
No
The function is disabled
Default
value
- No
Comment - This functionality allows for the calculation of rate of change
in a time unit defined by measurement timer
6.1.5.1.1.7. Alarm Hi
Function - The Hi alarm level for the computed increment of the
counter value
Data type - Number
Variation
range
- 0…65535
Default
value
- 0
Comment - This parameter allows using an alarm condition in the rules
processing
6.1.5.1.1.8. Alarm Lo
Function - The Lo alarm level for the computed increment of the
counter value
Data type - Number
Variation
range
- 0…65535
Default
value
- 0
Comment - This parameter allows using an alarm condition in the rules
processing
6.1.5.1.2. Binary input I3
The MT-703 module has a special binary input I3, which is factory connected with
a cover opening sensor. Activating this sensor causes immediate wake up of the
module, and then the information about the cover opening may be sent out. The
information may contain data packet or it may be a SMS message.
6.1.5.1.2.1. Name
Function - User friendly name of the I3 input (e.g., related to its