32
operation). This name is displayed on the list of connectors
Data type - Text
Variation
range
- Letters and digits, 16 characters maximum
Default
value
- I3
Comment - User friendly names of connectors help to distinguish their
destination as well as the required settings.
6.1.5.1.3. Analog inputs AN1, AN2
The MT-703 module has two identical analog inputs. Each analog input is
associated with the output of a supply voltage used for powering the analog signal
sensor. Such solution allows to minimize the energy consumption comparing to
continuous powering of a sensor.
Function - User friendly name for input (for example, the name based on
the input function)
Data type - Text
Variation
range
- Letters and digits, 16 characters maximum
Default
value
- The resource name, for example AN1 or AN2
Comment - User friendly names assigned to the connectors allow an easy
distinguish of their purposes and settings. The names are then
displayed on the connector list
6.1.5.1.3.1. Engineering units
Function - A name of the engineering unit used for measured values
Data type - Text
Variation
range
- Letters and digits, 16 characters maximum
Default
value
- x
Comment - n/a
6.1.5.1.3.2. Low reference - engineering units
Function - The low reference level for engineering units
Data type - Number
Variation
range
- 0…10000
Default
value
- 0
Comment - Together with remaining reference parameters, this one is
used to transform the physical input signal range to the
range expressed in engineering units
6.1.5.1.3.3. Low reference - internal units
Function - The low reference level for internal measuring units
Data type - Number
Variation - 0…1000