Goodrive300-01 inverter for air compressor Function parameters
-54-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
time-out period
Maintenance time-out function will be ineffective if it
is set to 0
P08.24
Motor temp
Range of display: 0~120
PT100 on the terminal board is used for detecting
motor temp value. When the value defined with
P8.25 is exceeded, temp fault OH will be reported
and the fault code is 37
0
P08.25
Motor overtemp
protection
0~130
0
P08.26
Counting mode of
maintenance time
0~1
0: Count during motor running
1: Count during motor running and sleeping
0
P08.27
Threshold for auto
frequency
reduction
Setting range: 0~130%
Auto frequency reduction will be applied when output
current exceeds P08.27
114%
P08.28
Fault reset times
Fault reset times: Set the automatic fault reset times.
If the reset time exceeds this set value, the inverter
will stop to wait maintenance.
Interval time of automatic fault reset: The interval
between the time when the fault occurs and the time
when the reset action occurs.
Setting range of P08.28: 0~10
Setting range of P08.29: 0.1~3600.0s
0
P08.29
Interval time of
automatic fault
reset
1.0s
P08.30
Frequency
decreasing ratio
of the dropping
control
The output frequency of the inverter changes as the
load. And it is mainly used to balance the power
when several inverters drive one load.
Setting range: 0.00~50.00Hz
0.00Hz
P08.31
Motor shifting
Goodrive300-01 supports the shift between two
motors. This function is used to select the shifting
channel.
LED ones: shifting channel
0: terminal shifting; digital terminal is 35
1: MODBUS communication shifting
2: Reserved
3: Reserved
4: Reserved
LED tens: shifting enabling in operation
0: Disabled
1: Enabled
0x00