Goodrive300-01 inverter for air compressor Function parameters
-55-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
0x00~0x14
P08.32
FDT1 electrical
level detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical level, the
multi-function digital output terminals will output the
signal of frequency degree test FDT until the output
frequency decreases to a value lower than (FDT
electrical levelFDT retention detection value) the
corresponding frequency, the signal is invalid. Below
is the waveform diagram:
Setting range of P08.32: 0.00Hz~P00.03 (Max.
output frequency)
Setting range of P08.33: -100.0~100.0% (FDT1
electrical level)
Setting range of P08.34: 0.00Hz~P00.03 (Max.
output frequency)
Setting range of P08.35: -100.0~100.0% (FDT2
electrical level)
50.00Hz
P08.33
FDT1 retention
detection value
5.0%
P08.34
FDT2 electrical
level detection
value
50.00Hz
P08.35
FDT2 retention
detection value
5.0%
P08.36
Frequency arrival
detection value
When the output frequency is among the positive or
negative detection range of the set frequency, the
multi-function digital output terminal will output the
signal of frequency arrival, see the diagram below
for detailed information:
Setting range: 0.00Hz~P00.03 (Max. output frequency)
0.00Hz