Goodrive300-LIFT series inverter    Communication protocol 
-124- 
P10.01 Load compensation time 0.000~5.000s 0.400
◎
Enable non-weighing
compensation
 
Note:  P29  group  is  the  factory  parameters  which  cannot  be  read  or  changed.  Some  parameters 
cannot be changed when the inverter is in the running state and some parameters cannot be changed 
in  any  state.  The  setting  range,  unit  and  relative  instructions  should  be  paid  attention  to  when 
modifying the function code parameters.   
Besides, EEPROM is stocked frequently, which may shorten the usage time of EEPROM. For users, 
some functions are not necessary to be stocked on the communication mode. The needs can be met 
on by changing the value in RAM. Changing the high bit of the function code form 0 to 1 can also 
realize the function. For  example, the function code  P00.07 is not stocked into EEPROM. Only by 
changing the value in RAM can set the address to 8007H. This address can only be used in writing 
RAM other than reading. If it is used to read, it is an invalid address. 
10.4.5.2 The address instruction of other function in Modbus 
The master  can operate on  the parameters of the  inverter as  well as control  the inverter,  such as 
running or stopping and monitoring the working state of the inverter.   
Below is the parameter list of other functions: 
Communication   
control command 
0006H: Coast to stop (emergency stop) 
The address of 
communication 
setting 
Communication setting frequency (0–Fmax, unit: 
0.01Hz)   
PID given, range (0–1000, 1000 corresponds 
to100.0%) 
PID feedback, range (0–1000, 1000 corresponds 
to100.0%) 
Torque setting value (-3000–3000, 1000 corresponds 
to the 100.0% of the rated current of the motor) 
The upper limit frequency setting during forward