0Hz.
Goodrive350 series inverter defines four groups of
acceleration and deceleration time, which can be
selected via multi-function digital input terminals
(P05 group). The acceleration/deceleration time of
the inverter is the first group by default.
Setting range of P00.11 and P00.12: 0.0–3600.0s
0: Run in default direction
1: Run in reverse direction
2: Reverse running is prohibited
Advantages of high carrier frequency are as follows:
ideal current waveform, few current harmonics and
small motor noise.
Disadvantages of high carrier frequency are as
follows: growing switch consumption, enlarged
temperature rise, impacted output capacity; under
high carrier frequency, the inverter needs to be
derated for use, meanwhile, the leakage current will
increase, which increases electromagnetic
interference to the surroundings.
While low carrier frequency is the contrary. Low
carrier frequency will cause unstable operation at
low frequency, decrease the torque, or even lead to