Goodrive350 series high-performance multi-function inverter Chapter 6
-167-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
1: Valid during running, clear after stop
2: Valid during running, clear after receiving stop
command
P08.45
UP terminal
frequency
incremental
integral rate
0.0150.00Hz/s
0.50Hz/s
P08.46
DOWN terminal
frequency
decremental
change rate
0.0150.00Hz/s
0.50Hz/s
P08.47
Action selection
for frequency
setup during
power down
0x0000x111
Ones: Action selection for frequency setup (by
keypad digits) during power down
0: Save during power down
1: Zero out during power down
Tens: Action selection for frequency setup (by
MODBUS) during power down
0: Save during power down
1: Zero out during power down
Hundreds: Action selection for frequency setup (by
other communication) during power down
0: Save during power down
1: Zero out during power down
0x000
P08.48
High bit of initial
value of power
consumption
Set the initial value of power consumption.
Initial value of power consumption=P08.48×1000+
P08.49
Setting range of P08.48: 059999 kWh (k)
Setting range of P08.49: 0.0999.9 kWh
P08.49
Low bit of initial
value of power
consumption
0.0°
P08.50
Flux braking
This function code is used to enable flux braking
function.
0: Invalid
100150: The larger the coefficient, the stronger the
brake intensity
The inverter enables motor to decelerate quickly by
increasing the motor flux which converts energy
generated during braking into thermal energy.
The inverter monitors motor state continuously even
0