Goodrive350 series high-performance multi-function inverter Chapter 6
-167-
Detailed parameter description
1: Valid during running, clear after stop
2: Valid during running, clear after receiving stop
command
UP terminal
frequency
incremental
integral rate
DOWN terminal
frequency
decremental
change rate
Action selection
for frequency
setup during
power down
0x000–0x111
Ones: Action selection for frequency setup (by
keypad digits) during power down
0: Save during power down
1: Zero out during power down
Tens: Action selection for frequency setup (by
MODBUS) during power down
0: Save during power down
1: Zero out during power down
Hundreds: Action selection for frequency setup (by
other communication) during power down
0: Save during power down
1: Zero out during power down
High bit of initial
value of power
consumption
Set the initial value of power consumption.
Initial value of power consumption=P08.48×1000+
P08.49
Setting range of P08.48: 0–59999 kWh (k)
Setting range of P08.49: 0.0–999.9 kWh
Low bit of initial
value of power
consumption
This function code is used to enable flux braking
function.
0: Invalid
100–150: The larger the coefficient, the stronger the
brake intensity
The inverter enables motor to decelerate quickly by
increasing the motor flux which converts energy
generated during braking into thermal energy.
The inverter monitors motor state continuously even