Goodrive350 series high-performance multi-function inverter Chapter 6
-166-
Detailed parameter description
700.0V;
660V
voltage:
1120.0V
Running mode of
cooling fan
0: Common running mode
1: The fan keeps running after power up
0x0000–0x1121
Ones: PWM mode
0: 3PH modulation and 2-phase modulation
1: 3PH modulation
Tens: PWM low-speed carrier limit
0: Limit low-speed carrier to 2K
1: Limit low-speed carrier to 4K
2: No limit on low-speed carrier
Hundreds: Reserved
Thousands: PWM loading mode
0: PWM loading mode 1
1: PWM loading mode 2
0x00–0x11
Ones
0: Overmodulation is invalid
1: Overmodulation is valid
Tens
0: Mild overmodulation
1: Deepened overmodulation
UP/DOWN
terminal control
setup
0x000–0x221
Ones: Frequency control selection
0: UP/DOWN terminal setup is valid
1: UP/DOWN terminal setup is invalid
Tens: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: All frequency modes are valid
2: Invalid for multi-step terminal when multi-step
speed takes priority
Hundreds: Action selection during stop
0: Valid