Goodrive350 series high-performance multi-function inverter Chapter 6
-165-
Detailed parameter description
Time t
Output frequency f
FDT level
FDT lag
Y1,
RO1, RO2
Time t
Setting range of P08.32: 0.00Hz–P00.03 (max.
output frequency)
Setting range of P08.33: 0.0–100.0% (FDT1 level)
Setting range of P08.34: 0.00Hz–P00.03 (max.
output frequency)
Setting range of P08.35: 0.0–100.0% (FDT2 level)
Detection value
for frequency
arrival
When the output frequency is within the positive
/negative detection range of the set frequency, the
multi-function digital output terminal outputs
"frequency arrival" signal as shown below.
Y,
RO1, RO2
Output frequency
Set
frequency
Detection amplitude
Time t
Time t
Setting range: 0.00Hz–P00.03 (max. output
frequency)
Enable/disable
energy-
consumption
brake
0: Disable energy-consumption
1: Enable energy-consumption
Energy-
consumption
brake threshold
voltage
Set the starting bus voltage of energy-consumption
brake, adjust this value properly can brake the load
effectively. The default value will change with the
change of voltage class.
Setting range: 200.0–2000.0V
220V
voltage:
380.0V;
380V
voltage: