EasyManua.ls Logo

INVT Goodrive350 Series

INVT Goodrive350 Series
341 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive350 series high-performance multi-function inverter Chapter 6
-165-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
Time t
Output frequency f
FDT level
FDT lag
Y1,
RO1, RO2
Time t
Setting range of P08.32: 0.00HzP00.03 (max.
output frequency)
Setting range of P08.33: 0.0100.0% (FDT1 level)
Setting range of P08.34: 0.00HzP00.03 (max.
output frequency)
Setting range of P08.35: 0.0100.0% (FDT2 level)
P08.36
Detection value
for frequency
arrival
When the output frequency is within the positive
/negative detection range of the set frequency, the
multi-function digital output terminal outputs
"frequency arrival" signal as shown below.
Y,
RO1, RO2
Output frequency
Set
frequency
Detection amplitude
Time t
Time t
Setting range: 0.00HzP00.03 (max. output
frequency)
0.00Hz
P08.37
Enable/disable
energy-
consumption
brake
0: Disable energy-consumption
1: Enable energy-consumption
1
P08.38
Energy-
consumption
brake threshold
voltage
Set the starting bus voltage of energy-consumption
brake, adjust this value properly can brake the load
effectively. The default value will change with the
change of voltage class.
Setting range: 200.02000.0V
220V
voltage:
380.0V;
380V
voltage:

Table of Contents

Related product manuals