Goodrive350 series high-performance multi-function inverter Chapter 6
-176-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
0: Disable software input phase loss protection
1: Enable software input phase loss protection
Tens:
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds:
0: Disable hardware input phase loss protection
1: Enable hardware input phase loss protection
P11.01
Frequency-drop
at transient
power down
0: Disable
1: Enable
0
P11.02
Reserved
variables
065535
0
P11.03
Overvoltage stall
protection
0: Disable
1: Enable
Overvoltage stall
threshold
Output
frequency
Time t
Time t
DC bus voltage V
1
P11.04
Overvoltage stall
protection
voltage
120150% (standard bus voltage) (380V)
136%
120150% (standard bus voltage) (220V)
120%
P11.05
Current-limit
selection
During accelerated running, as the load is too large,
the actual acceleration rate of motor is lower than
that of output frequency, if no measures are taken,
the inverter may trip due to overcurrent during
acceleration.
0x000x11
Ones: Current-limit action selection
0: Invalid
1: Always valid
Tens: Hardware current-limit overload alarm
selection
0: Valid
1: Invalid
01