Goodrive350 series high-performance multi-function inverter Chapter 6
-177-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P11.06
Automatic
current-limit level
Current-limit protection function detects output
current during running, and compares it with the
current-limit level defined by P11.06, if it exceeds the
current-limit level, the inverter will run at stable
frequency during accelerated running, or run in
decreased frequency during constant-speed
running; if it exceeds the current-limit level
continuously, the inverter output frequency will drop
continuously until reaching lower limit frequency.
When the output current is detected to be lower than
the current-limit level again, it will continue
accelerated running.
Output current A
Output frequency f
Current-limit
threshold
Set
frequency
Acceleration
Constant
speed
Time t
Time t
Setting range of P11.06: 50.0200.0%
Setting range of P11.07: 0.0050.00Hz/s
G model:
160.0%
P model:
120.0%
P11.07
Frequency-drop
rate during
current limit
10.00
Hz/s
P11.08
Inverter or motor
overload/underlo
ad pre-alarm
If the inverter or motor output current is larger than
the overload pre-alarm detection level (P11.09), and
the duration exceeds the overload pre-alarm
detection time (P11.10), overload pre-alarm signal
will be outputted.
Y,
RO1, RO2
Output current
Overload pre-alarm
threshold
Time t
Time t
Pre-alarm time tPre-alarm time t
Setting range of P11.08:
0x000
P11.09
Overload
pre-alarm
detection level
G model:
150%
P model:
120%
P11.10
Overload
pre-alarm
detection time
1.0s