Goodrive350 series high-performance multi-function inverter Chapter 6
-188-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
card slot 2
P16.29
Communication
timeout period of
extension card in
card slot 3
0.0600.0s
If it is set to 0.0, offline fault will not be detected
/
/
P16.30
P16.69
Reserved
P17 group State-check functions
P17.00
Set frequency
Display current set frequency of the inverter.
Range: 0.00HzP00.03
50.00Hz
P17.01
Output frequency
Display current output frequency of the inverter.
Range: 0.00HzP00.03
0.00Hz
P17.02
Ramps reference
frequency
Display current ramps reference frequency of the
inverter.
Range: 0.00HzP00.03
0.00Hz
P17.03
Output voltage
Display current output voltage of the inverter.
Range: 01200V
0V
P17.04
Output current
Display the valid value of current output current of
the inverter.
Range: 0.05000.0A
0.0A
P17.05
Motor speed
Display current motor speed.
Range: 065535RPM
0 RPM
P17.06
Torque current
Display current torque current of the inverter.
Range: -3000.03000.0A
0.0A
P17.07
Exciting current
Display current exciting current of the inverter.
Range: -3000.03000.0A
0.0A
P17.08
Motor power
Display current motor power; 100% relative to rated
motor power, positive value is motoring state,
negative value is generating state.
Range: -300.0300.0% (relative to rated motor
power)
0.0%
P17.09
Motor output
torque
Display current output torque of the inverter; 100%
relative to rated motor torque, during forward
running, positive value is motoring state, negative
value is generating state, during reverse running,
positive value is generating state, negative value is
motoring state.
Range: -250.0250.0%
0.0%

Table of Contents