Goodrive350 series high-performance multi-function inverter Chapter 6
-212-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P25 group Extension I/O card input functions
P25.00
HDI3 input type
selection
0: HDI3 is high-speed pulse input
1: HDI3 is digital input
0
P25.01
S5 terminal
function
The same with P05 group
0
P25.02
S6 terminal
function
0
P25.03
S7 terminal
function
0
P25.04
S8 terminal
function
0
P25.05
S9 terminal
function
0
P25.06
S10 terminal
function
0
P25.07
HDI3 terminal
function
0
P25.08
Input terminal
polarity of
extension card
0x000x7F
0x00
P25.09
Virtual terminal
setup of
extension card
0x0000x7F (0: disable, 1: enable)
BIT0: S5 virtual terminal
BIT1: S6 virtual terminal
BIT2: S7 virtual terminal
BIT3: S8 virtual terminal
BIT4: S9 virtual terminal
BIT5: S10 virtual terminal
BIT6: HDI3 virtual terminal
0x00
P25.10
HDI3 terminal
switch-on delay
These function codes define corresponding delay of
the programmable input terminals during level
variation from switch-on to switch-off .
Si electrical level
Si valid
invalid invalid
Switcn-on
delay
Switcn-off
delay
valid
Setting range: 0.00050.000s
0.000s
P25.11
HDI3 terminal
switch-off delay
0.000s
P25.12
S5 terminal
switch-on delay
0.000s
P25.13
S5 switch-off
delay
0.000s
P25.14
S6 terminal
switch-on delay
0.000s

Table of Contents