Goodrive350 series high-performance multi-function inverter Chapter 6
-214-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
setting of upper
limit of AI4
anti-interference capacity of analog variables;
however, it will also degrade the sensitivity of analog
input.
Note: AI3 and AI4 can support 010V/020mA input,
when AI3 and AI4 select 020mA input, the
corresponding voltage of 20mA is 10V;
Setting range of P25.24: 0.00VP25.26
Setting range of P25.25: -100.0%100.0%
Setting range of P25.26: P25.2410.00V
Setting range of P25.27: -100.0%100.0%
Setting range of P25.28: 0.000s10.000s
Setting range of P25.29: 0.00VP25.31
Setting range of P25.30: -100.0%100.0%
Setting range of P25.31: P25.2910.00V
Setting range of P25.32: -100.0%100.0%
Setting range of P25.33: 0.000s10.000s
P25.33
Input filter time of
AI4
0.030s
P25.34
HDI3 high-speed
pulse input
function
0: Set input via frequency
1: Count
0
P25.35
Lower limit
frequency of
HDI3
0.000 KHz P25.37
0.000
KHz
P25.36
Corresponding
setting of lower
limit frequency of
HDI3
-100.0%100.0%
0.0%
P25.37
Upper limit
frequency of
HDI3
P25.35 50.000KHz
50.000
KHz
P25.38
Corresponding
setting of upper
limit frequency of
HDI3
-100.0%100.0%
100.0%
P25.39
HDI3 frequency
input filter time
0.000s10.000s
0.030s
P25.40
AI3 input signal
type
Range: 01
0: Voltage type
1: Current type
0