Goodrive350 series high-performance multi-function inverter Chapter 5
-62-
Function
code
Name
Detailed parameter description
Default
value
P04.27
Channel of voltage setup
0: Keypad; output voltage is determined by
P04.28
1: AI1
2: AI2
3: AI3
4: HDIA
5: Multi-step
6: PID
7: MODBUS communication
8: PROFIBUS/CANopen communication
9: Ethernet communication
10: HDIB
11: EtherCat/Profinet communication
12: PLC card
13: Reserved
0
P04.28
Set voltage value via keypad
0.0%100.0% (rated motor voltage)
100.0%
P04.29
Voltage increase time
0.03600.0s
5.0s
P04.30
Voltage decrease time
0.03600.0s
5.0s
P04.31
Output max. voltage
P04.32100.0% (rated motor voltage)
100.0%
P04.32
Output min. voltage
0.0%P04.31 (rated motor voltage)
0.0%
5.5.5 Torque control
GD350 inverter supports torque control and speed control. Speed control mode aims to stabilize the
speed to keep the set speed consistent with the actual running speed, meanwhile, the max.
load-carrying capacity is restricted by torque limit. Torque control mode aims to stabilize the torque to
keep the set torque consistent with the actual output torque, meanwhile, the output frequency is
restricted by upper/lower limit.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive350 Series and is the answer not in the manual?

INVT Goodrive350 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive350 Series
CategoryDC Drives
LanguageEnglish

Related product manuals