SPC Series Solar Pump Inverter Function parameter list
-22-
Function
code
Name
Description
Default
Modify
Note:
When the parameter is restored to
the default value, the motor's
running direction is restored to the
default one. Exercise caution before
using this function if the change of
motor rotation direction is
disallowed after commissioning.
Do not change the setting of the
parameter because reverse running
is not allowed in water pump
application scenarios.
2: Disable reverse running. It can be
used in some special scenarios where
reverse running is disallowed.
P00.15
Motor
parameter
autotuning
0: No operation
1: Rotary autotuning
Comprehensive motor parameter
autotuning. It is recommended to use
rotating autotuning when high control
accuracy is needed.
2: Static autotuning 1
Used in scenarios where the motor
cannot be disconnected from load.
3: Static autotuning 2
Empty-load current and mutual
inductance are not autotuned.
0
P00.18
Function
parameter
restore
0: No operation
1: Restore default values
2: Clear fault records
Note:
After the selected operation is
performed, the function code is
automatically restored to 0.
Restoring the default values may
delete the user password. Exercise
caution before using this function.
0