SPC Series Solar Pump Inverter Fault diagnosis and solution
-52-
Fault code
Fault type
Possible cause
Solution
communication
wiring.
The communication
address is incorrect.
There is strong
interference to the
communication.
interface wiring.
Set a proper
communication
address.
Change or replace the
wire or improve the
anti-interference
capability.
ItE
Current detection
fault
The control board
connector is in poor
contact.
Hall device is
damaged.
An exception occurs
on the magnifying
circuit.
Check the connector
and re-plug.
Replace the Hall
device.
Change the main
control board.
tE
Motor autotuning
fault
The motor capacity
does not match the
inverter capacity.
Motor parameters
are not set correctly.
The difference
between the
parameters obtained
from autotuning and
the standard ones is
great.
Autotuning timed out.
Change the inverter
model.
Set the motor type and
nameplate parameters
correctly.
Empty the motor load.
Check the motor wiring
and parameter settings.
Check whether the
upper limit frequency is
higher than 2/3 of the
rated frequency.
EEP
EEPROM
operation error
Error in reading or
writing control
parameters.
The EEPROM is
damaged.
Press STOP/RST for
reset.
Change the main
control board.
END
Running time
reached
The actual running
time of the inverter is
longer than the
internal set running
time.
Ask for the supplier and
adjust the set running
time.