The boiler has the “chimney-sweeper” funcon, forcing burner ignion at the maximum output not
modulated. This funcon allows more reliable measurements of those obtained when the gas boiler is
acvated through the room thermostat or hot water demands.
f Prepare the instruments for combuson checking;
f acvate the “chimney-sweeper” funcon, following this simple procedure, studied to avoid acciden-
tal acvaons of the user;
• supply the boiler and turn the Summer/Winter knob
to Summer posion ;
• provide that room thermostat contact is closed (acvated) or open an hot water tap (the heat
produced by the boiler will be drained consequently);
• turn the Hot Water knob
to the posion Chimney-sweeper and wait (about 5 seconds)
that the display shows “SE” (SErvice) ashing (moreover, lamp ashes with short pulses);
• when the display shows “SE” ashing, turn the Hot Water knob
on the scale . The indica-
on service appears on the display and the burner ignites at the maximum output not modulated
(the YELLOW light turns on);
f make the checks and measurements;
f switch o the burner, by turning the Summer/Winter knob
to the posion. The
light blinks.
Remark: the burner will switch o automacally when reaching the maximum temperature, and in
any case aer 15 minutes.
The pump has a selector which allows to reduce the speed, so as to reduce the noise produced by the
too rapid circulaon of the liquids in too small heang systems.
• III = Maximum Speed (Factory seng)
• II = Medium Speed
• I = Minimum Speed (use only if strictly neces-
sary; test the heang system, verifying that no
overheang problems occur).