16
Make sure that the hydraulic and heang systems ducts
the electrical system. They are absolutely NOT SUITABLE for such a use. Besides: they don't
guarantee the earth dispersion; in case of electrical fault they could generate a fulguraon risk;
there could take place galvanic currents in the pipings and consequent corrosion and hydraulic
leaks.
Advices and suggesons to avoid vibraons and noises in the system
f Do not use pipes with reduced diameters;
f Do not use bends with small radius and reducons of important secons.
Cleaning and preservaon of the systems
The eciency, the reliability and the safety of the boilers, as all generic thermal systems and compo-
nents, depend strictly on the features of the water that supply them and on their treatment.
A proper treatment of the water improves the protecon of the systems against corrosions (and there-
fore perforaons, noise, leaks, etc.) and limestone incrustaons that drascally reduce the eciency
of the thermal exchange (consider that 1 mm of limestone incrustaons reduces of 18% the thermal
exchange of the heang element on which it has been formed).
ITALTHERM guarantees its products only if the characteriscs of the water comply with UNI 8065, re-
ported also in laws on energy saving.
Thoroughly wash the heang system with water, before connecng the boiler. This will elimi-
nate residual like welding drops, slag, hemp, masc, mud, rust and other dirt from pipes and
radiators. Otherwise, these substances could enter the boiler and damage the internal compo-
nents (pump etc.).
f , in the
suitable quanty and following the instrucons of its manufacturer.
f If the water on boiler inlet is harder than 25° fr, it’s required to install a soener to bring the hardness
below that value, as required by the reference regulaon.
f For oor system and generally all low temperature systems, the water treatment product must have
lming acon (protecon against corrosion and incrustaon) and acon against bacteria and algae.
Heang system
f Connect the safety evacuaon ducts of the boiler to an evacuaon funnel. If safety valves are not
connected to an evacuaon device, their intervenon could ood the room. The manufacturer can-
not be held responsible for any damage arising from that situaon.
Once all system connecons have been carried out, proceed with system lling. This operaon should
be made with care, respecng the following steps:
f Open the radiators venng devices;
f Check that the plug of the automac air vent, incorporated in the boiler circulator, is unscrewed: if
not, unscrew it and leave it unscrewed, even aerwards, for normal operaon;
f If it's required to ll the system with an-freeze soluon, do this operaon, then hermecally close
the connecon or the valve used to put the soluon in, to allow the pressurizaon.
f Gradually open the lling cock 1 ;